Sale!

Mini Chiller Training System with Modular Refrigeration and Thermal Storage

Original price was: ₹670,000.00.Current price is: ₹425,000.00.

The Mini Chiller Training System with Modular Refrigeration and Thermal Storage is a comprehensive, self-contained pilot-scale thermal engineering plant designed specifically for advanced educational institutions and research laboratories. This training rig gives mechanical, refrigeration, and HVAC engineering students hands-on access to practical energy-shifting technologies and modular refrigeration circuit analysis.

Available on backorder

SKU: AL-RTS-MCRCTS-01 Category: Brand:

Product Overview

The Mini Chiller Training System with Modular Refrigeration and Thermal Storage is a comprehensive, self-contained pilot-scale thermal engineering plant designed specifically for advanced educational institutions and research laboratories. This training rig gives mechanical, refrigeration, and HVAC engineering students hands-on access to practical energy-shifting technologies and modular refrigeration circuit analysis.

The apparatus effectively simulates standard commercial building peak-load management by utilizing a highly efficient water-chiller circuit combined with modular thermal storage to generate and store thermal energy (as ice) during low-demand periods, subsequently discharging it to satisfy cooling loads without high electrical power drawing.

System Composition & Component Specifications

No. Component Technical Parameters / Specifications Qty
1 Condensing Unit Hermetic/Scroll Compressor assembly operating with eco-friendly R134A refrigerant loop (integrated with a Variable Frequency Drive (VFD) calibrated to convert 60Hz input power frequency to a stable 50Hz operational frequency). Power input: 750W, Nominal refrigerating capacity: 1750W at -15/32°C conditions approx. 1 Set
2 Ice Storage Tank 150L storage volume approx. Heavily insulated double-wall SS304 tank containing high-density polyurethane insulation and dense internal copper heat exchanger coils. 1 Set
3 Plate Heat Exchanger Compact, AISI 316 Stainless Steel brazed plate heat exchanger operating as high-efficiency refrigeration loop evaporator. Cooling capacity approx: 1500 to 2000 W. 1 pc
4 Secondary Glycol Tank 28L fluid capacity approx. Serves as open expansion and mixing tank reservoir for the anti-freeze water-glycol heat transfer charging solution. 1 pc
5 Shell & Tube Condenser Industrial-grade shell and multi-tube water-cooled condenser with copper tube bundle for efficient heat extraction. Cooling capacity approx: 2000 to 2500 W. 1 pc
6 Mechanical Cooling Tower FRP open-type wet cooling tower with integrated axial fan system for condensing-loop heat rejection to ambient environment. Cooling capacity approx: 2000 to 2500 W. 1 pc
7 Circulation Pumps Two high-reliability centrifugal pumps layout: 1x for the Condenser Water loop, 1x for the low-temperature Glycol-Water solution loop. 2 pcs
8 Mobile Mounting Rig Rugged, ergonomic mild steel (MS) square section frame structure, finished with rust-resistant industrial powder coating and 4 locking caster wheels. 1 pc

General Technical Parameters

  • Overall Dimensions: 2000 mm (W) × 700 mm (D) × 1850 mm (H)

  • Dry System Weight: Approx. 200 kg

  • Utility Requirements: Single-Phase, AC 230V, 50Hz electrical supply connection (with built-in VFD frequency conversion support)

  • Primary Charge: Refrigerant R134a Gas / Aqueous Glycol Mixing Agent

Analog Instrumentation & Manual Controls

The apparatus features complete manual fluid circuit controls, allowing absolute control over mode changes without software dependency, reinforcing structural mechanical tracking skills:

  • Pressure Indicators: Dial gauges mounted on the refrigeration manifold (Low Pressure: -1 to 9 bar, High Pressure: -1 to 24 bar).

  • Variable Flow Meters: Variable area inline rotameters calibrated for fluid measurement across a range of 8 to 102 L/h.

  • Thermal Measurement Panel: Multi-channel digital temperature scanner connected to local immersion PTD / type-K thermocouples (measuring ranges from -20°C to 60°C) across all heat-exchanger terminals.

  • Flow Control Manifold: Industrial-grade brass 3-way manual valves and isolating ball valves strategically placed to switch loop configurations.

Laboratory Experiments & Exercises

  • Introduction to Modular Refrigeration & Thermal Storage: Visualizing the mechanics of commercial chilled water plants and peak-load shifting strategies.

  • Fluid Loop Routing & Balancing: Tracing and calculating flow behaviors inside the R134a loop, secondary glycol loop, and open cooling water loop.

  • Ice Production Operation (Charging Mode): Measuring charging time, refrigeration plant input, and temperature drop profile during ice buildup via VFD-assisted power regulation.

  • Cooling Load Delivery Operation (Discharging Mode): Deactivating the core refrigeration plant and running purely off ice-melting thermal power delivery.

  • Thermodynamic Performance Evaluation: Manually logging data points to calculate the system Coefficient of Performance (COP) and creating complete heat energy balances.